NQA
European Commission project  for your
Life & the Environment click here

Water Quality Monitoring Instrumentation

Environmental & sustainable water treatment to save the planet

free hit
counter

factory.jpg (3825 bytes)

| Homepage | Contact us  | About us |  Shop ||

| Index for instruments | Oxygen probes | AquaTraul O2 monitors |  Refractometers | bacterial dip slides | Total Gas | Float switch |

Conductivity Controller

industrial instruments homepage | buy or view price | manual

  • Ten Selectable Conductivity Measurement Ranges in one controller via its IP54 front panel. High-level accuracy of �1% of full scale can be obtained with appropriate cells and correct temperature coefficient
  • User-Customization through Setup Menu in matching the functions to suit specific operation
  • Tri-Level Password Protection against authorized tampering
  • Non-Volatile Memory retains all stored measurement parameters and calibration data
  • Selectable Cell Constant (0.01, 0.1, 1.0, 10.0) to cater for different applications for more accurate measurements
  • Two contact relays and 1 Alarm Relay with independent timer control
  • Hysteresis Band Protection against rapid control switching of relays from wear and tear
  • Temperature Coefficient for more accurate measurement with a pure water compensation option available to automatically compensate for linearity in linear/pure water applications
  • Line Resistance Compensation against intrinsic cable resistance for longer cable connection
  • Choice of Temperature Sensor Pt100/Pt1000 with 2-wire or 3-wire temperature input selection
  • Electrode Diagnosis can be obtained after each successful calibration with cell characteristics displayed, useful for tracking the cell efficiency
  • Scalable  0/4..20 mA transmitter isolated output for use to maximize the resolution on the chart recorder
  • IP54 rated front panel against dust and accidental water spills
  • Installation and wiring are easily performed with detachable plug-in connectors
 

The microprocessor-based  conductivity controller is CE and UL certified in compliance to meet international standards against electromagnetic interference. Ideal for power plant, drinking water, boiler and cooling towers, water treatment applications.

Specifications

Product Code  
Conductivity Range 0.000-1.999, 19.99, 199.9, 1999.9, 
5000 �S/cm; 0.00-19.99, 199.9 mS/cm
Resolution & Accuracy 0.001, 0.01, 0.1, 1 �S/cm; 0.01, 0.1 mS/cm
 & � 1% Full Scale
Cell constants 0.01, 0.1, 1.0, 10.0 (s/w selectable)
Signal output range (0/4 - 20 mA) Max. 100% Full Scale; Min. 10% Full Scale
Temperature Range -9.9 to 125.0 oC
Resolution & Accuracy 0.1 oC & � 0.5 oC
Sensor (for ATC) PT100/PT1000
Type of Controller Setting Limit
Pickup/Dropout Delay 0 to 2000 seconds
No. of Relays
Maximum Voltage
Maximum Current
High/Low Hysteresis Band
2 SPDT; 1 Alarm
250 VAC
3A; 
0 to 10% Full Scale
Contact Set-points Lo/Lo; Lo/Hi; Hi/Lo; Hi/Hi (selectable)
Alarm Function Latching / Pulse (software)
Power Requirement 120 or 240 VAC
Dimensions 1/4 DIN (96 x 96 mm)